2016-11-30 19:06:09PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW: NO MECHANICAL
 PLANS WERE SUBMITTED.
  
 1) SHOW THAT THE ADDITION IS IN COMPLIANCE WITH
 FBC-R303.9 REQUIRED HEATING.
 WHEN THE WINTER DESIGN TEMPERATURE IN TABLE R301.2(1)
 IS BELOW 60 DEGRESS F , EVERY DWELLING UNIT SHALL BE
 PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING
 A MINIMUM ROOM TEMPERATURE OF 68 DEGREES F AT A POINT 3
 FEET (914 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM
 EXTERIOR WALLS IN ALL HABITABLE ROOMS AT THE DESIGN
 TEMPERATURE. THE INSTALLATION OF ONE OR MORE PORTABLE
 SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE
 WITH THIS SECTION.
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16.