| 2016-11-30 19:06:09 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: NO MECHANICAL | | | PLANS WERE SUBMITTED. | | | | | | 1) SHOW THAT THE ADDITION IS IN COMPLIANCE WITH | | | FBC-R303.9 REQUIRED HEATING. | | | WHEN THE WINTER DESIGN TEMPERATURE IN TABLE R301.2(1) | | | IS BELOW 60 DEGRESS F , EVERY DWELLING UNIT SHALL BE | | | PROVIDED WITH HEATING FACILITIES CAPABLE OF MAINTAINING | | | A MINIMUM ROOM TEMPERATURE OF 68 DEGREES F AT A POINT 3 | | | FEET (914 MM) ABOVE THE FLOOR AND 2 FEET (610 MM) FROM | | | EXTERIOR WALLS IN ALL HABITABLE ROOMS AT THE DESIGN | | | TEMPERATURE. THE INSTALLATION OF ONE OR MORE PORTABLE | | | SPACE HEATERS SHALL NOT BE USED TO ACHIEVE COMPLIANCE | | | WITH THIS SECTION. | | | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | 3) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | | PER FBC-R M16. |
|