| 2016-11-16 14:01:04 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE AN ELECTRICAL DETAIL TO INCLUDE WIRE & | | | CONDUIT SIZE, EQUIPMENT DISCONNECT LOCATION, AND OVER | | | CURRENT PROTECTION SIZE. | | | | | | 2] PROVIDE MANUFACTURE SPECIFICATIONS. |
|