| Plan Review Notes For Permit 16100814 |
| Permit Number |
16100814 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-03 13:09:05 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE A ONE-LINE DIAGRAM SHOWING CONDUIT AND WIRE | | | SIZE FEEDING THE PROPOSED SHED, SHOW PANEL SCHEDULE | | | IDENTIFYING OVER CURRENT PROTECTION AMPERE RATING. | | | FBC-107 | | | | | | 2] IF THE SEPERATE STRUCTURE IS SUPPLIED WITH MORE THAN | | | A SINGLE FEEDER BRANCH CIRCUIT INCLUDING A MULTIWIRE | | | CIRCUIT A GROUNDING ELECTRODE SYSTEM SHALL BE INSTALLED | | | PER FBC-R SECTION E3607.3. | | | | | | 3] PLEASE ADD A SWITCHED CONTROLLED LIGHTING OUTLET IN | | | THE BACK EGRESS DOOR IN ACCORDANCE WITH FBC-R SECTION | | | E3903.3 |
|