Plan Review Notes
Plan Review Notes For Permit 16100812
Permit Number 16100812
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-23 15:48:121ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE OVERALL WIDTH OF THE ACCESSIBLE BATHROOM NEEDS
 TO BE A MIN OF 84" TO ALLOW FOR THE 60'X54" TOILET
 CLEARANCE IT CAN NOT HAVE ANY OTHER FIXTURES IN IT .
 AND THE CLEARANCE REQUIRED FOR THE LAVATORY. PER FBC
 ACC 603/ 604.3.2 OVERLAP.
 THE REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 2. THE PLAN NOTES A HI LO EWC BUT IT SHOWS A SINGLE A
 MINIMUM OF TWO IS REQUIRED FBC ACC 211.2 MINIMUM
 NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 PLEASE CLARIFY.
  
 3. THE CLEAR FLOOR SPACE FOR THE WATER FOUNTAIN IS
 SHOWN EXTENDING INTO THE WALL PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 4. THE SIDE WALL GRAB BAR SHALL COMPLY WITH FBC ACC
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 THE DETAIL SHOWING THE BACKING FOR GRAB BAR DOES NOT
 COMPLY PLEASE REMOVE. PER WPB AMEND TO FBC 107.2.1
  
 5. THE HIGHT OF THE GRAB BAR SHALL COMPLY FBC ACC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 6. TOILET PAPER DISPENSER SHALL BE 7" TO 9" MEASURED
 OFF THE FRONT OF THE TOILET. PER FBC ACC 604.7
  
 7. PLEASE PROVIDE SANITARY AND WATER RISER DIAGRAM. PER
 WPB AMEN TO FBC 107.3.5.1.3(13)
  
 8. PLEASE PROVIDE OCCUPANT LOAD AND NUMBER OF EXISTING
 BATHROOMS . PER WPB AMEND TO FBC 107.2.1
  
 9. PLEASE PROVIDE THE SPECIFIC CODES PROJECT IS BEING
 DESIGNED TO. PER WPB AMEND TO FBC 107.2.1