| Plan Review Notes For Permit 16100812 |
| Permit Number |
16100812 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-07 14:11:01 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] ALL RECEPTACLES INSTALLED IN BATHROOMS SHALL BE GFCI | | | PROTECTED IN ACCORDANCE WITH NEC 210.8(B)(1). SHOW | | | COMPLIANCE. | | | | | | 2] PROVIDE AN ADA DETAIL FOR OBSTRUCTED & UNOBSTRUCTED | | | REACH RANGES OF DEVICES PER FBC-A SECTION 308. | | | | | | 3] CLARIFY IF THE SCOPE OF WORK INCLUDES DRINKING | | | FOUNTAIN INSTALLATION ? IF SO PLEASE SHOW THE DEDICATED | | | RECEPTACLE OUTET WITH GFCI PROTECTION PER NEC 422.52. |
|