| 2016-11-04 07:58:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PLAN CONFLICTS WITH APPLICATION; SCOPE NOT CLEAR, |
| | FBC 107. |
| | |
| | THE APPLICATION WORK DESCRIPTION DESCRIBES A BATHROOM |
| | AND GIVES AN NOA NUMBER FOR A DOOR. THE NOA WAS NOT |
| | PROVIDED. ALUMINUM WINDOW WALL NOAS WERE PROVIDED. THE |
| | PLANS DO NOT SHOW WINDOW WALL OR DOOR REPLACEMENT. |
| | VALUE ON APPLICATION APPEARS TOO LOW. |
| | |
| | REVISE PLAN TO SHOW ALL WORK PROPOSED. PROVIDE PRODUCT |
| | APPROVALS FOR COMPONENTS AND CLADDING IN THE SCOPE OF |
| | THIS PERMIT. DESIGNER OF RECORD IS TO REVIEW PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL. |
| | |
| | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC |
| | 109. |
| | |
| | 3. REVISE PLAN TO SHOW 18 INCH MANEUVERING CLEARANCE, |
| | PULL SIDE, FOR THE BATHROOM DOOR, FBC 5TH EDITION |
| | ACCESSIBILITY 404.2.4. |
| | |
| | 4. IF COMPONENTS AND CLADDING ARE TO BE INCLUDED IN THE |
| | SCOPE OF THIS PERMIT, REVISE PLAN TO INCLUDE WIND |
| | DESIGN CRITERIA FBC 1603.1.4. |
| | |
| | 5. THERE IS AN OUTDATED CODE REFERENCE ON SHEET 2 (FBC |
| | 11 430), REVISE. |
| | |
| | 6. FBC 5TH EDITION ACCESSIBILITY 609.4, THE GRAB BAR IS |
| | SHOWN AS 36 IN TO THE CENTER OF THE BAR, THIS IS TO |
| | MEASURED TO THE TOP (SO THE DETAIL DOES NOT COMPLY), |
| | REVISE. |
| | |
| | 7. FBC 5TH EDITION ACCESSIBILITY 604.4, THE WATER |
| | CLOSET IS TO BE MEASURED TO THE TOP OF THE SEAT. DETAIL |
| | 4, SHEET 2 IS NOT CLEAR. THE DIMENSION IS SHOWN TO THE |
| | TOP OF THE FIXTURE, WHICH IS USUALLY THE TOP OF THE LID |
| | (NOT THE SEAT). REVISE DETAIL TO CLARIFY. |
| | |
| | 8. SHOW ACCESSIBLE ROUTE TO THE ALTERED AREA, FBC 5TH |
| | EDITION 202.3. REVISE THE PLAN TO SHOW ACCESSIBLE ROUTE |
| | AND INCLUDE THE FLOOR PLAN TO SHOW HOW THE EXISTING |
| | SPACE WILL BE AFFECTED BY THE PROPOSED RENOVATION, FBC |
| | 107, FBC CHAPTER 10. |
| | |
| | 9. IF ENTRY DOOR REPLACEMENT IS PROPOSED, PROVIDE THE |
| | PRODUCT APPROVAL (REVIEWED BY THE DESIGNER OF RECORD), |
| | AND INDICATE HARDWARE PROPOSED. REVISE PLAN TO INCLUDE |
| | OCCUPANCY CLASSIFICATION FOR THE AREAS AFFECTED BY THE |
| | NEW ENTRY DOOR. PANIC HARDWARE REQUIRED FOR A, E AND H |
| | OCCUPANCIES, FBC 1008.1.10. |
| | |
| | |
| | |