2016-11-04 07:58:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLAN CONFLICTS WITH APPLICATION; SCOPE NOT CLEAR,
 FBC 107.
  
 THE APPLICATION WORK DESCRIPTION DESCRIBES A BATHROOM
 AND GIVES AN NOA NUMBER FOR A DOOR. THE NOA WAS NOT
 PROVIDED. ALUMINUM WINDOW WALL NOAS WERE PROVIDED. THE
 PLANS DO NOT SHOW WINDOW WALL OR DOOR REPLACEMENT.
 VALUE ON APPLICATION APPEARS TOO LOW.
  
 REVISE PLAN TO SHOW ALL WORK PROPOSED. PROVIDE PRODUCT
 APPROVALS FOR COMPONENTS AND CLADDING IN THE SCOPE OF
 THIS PERMIT. DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS PRIOR TO SUBMITTAL.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 3. REVISE PLAN TO SHOW 18 INCH MANEUVERING CLEARANCE,
 PULL SIDE, FOR THE BATHROOM DOOR, FBC 5TH EDITION
 ACCESSIBILITY 404.2.4.
  
 4. IF COMPONENTS AND CLADDING ARE TO BE INCLUDED IN THE
 SCOPE OF THIS PERMIT, REVISE PLAN TO INCLUDE WIND
 DESIGN CRITERIA FBC 1603.1.4.
  
 5. THERE IS AN OUTDATED CODE REFERENCE ON SHEET 2 (FBC
 11 430), REVISE.
  
 6. FBC 5TH EDITION ACCESSIBILITY 609.4, THE GRAB BAR IS
 SHOWN AS 36 IN TO THE CENTER OF THE BAR, THIS IS TO
 MEASURED TO THE TOP (SO THE DETAIL DOES NOT COMPLY),
 REVISE.
  
 7. FBC 5TH EDITION ACCESSIBILITY 604.4, THE WATER
 CLOSET IS TO BE MEASURED TO THE TOP OF THE SEAT. DETAIL
 4, SHEET 2 IS NOT CLEAR. THE DIMENSION IS SHOWN TO THE
 TOP OF THE FIXTURE, WHICH IS USUALLY THE TOP OF THE LID
 (NOT THE SEAT). REVISE DETAIL TO CLARIFY.
  
 8. SHOW ACCESSIBLE ROUTE TO THE ALTERED AREA, FBC 5TH
 EDITION 202.3. REVISE THE PLAN TO SHOW ACCESSIBLE ROUTE
 AND INCLUDE THE FLOOR PLAN TO SHOW HOW THE EXISTING
 SPACE WILL BE AFFECTED BY THE PROPOSED RENOVATION, FBC
 107, FBC CHAPTER 10.
  
 9. IF ENTRY DOOR REPLACEMENT IS PROPOSED, PROVIDE THE
 PRODUCT APPROVAL (REVIEWED BY THE DESIGNER OF RECORD),
 AND INDICATE HARDWARE PROPOSED. REVISE PLAN TO INCLUDE
 OCCUPANCY CLASSIFICATION FOR THE AREAS AFFECTED BY THE
 NEW ENTRY DOOR. PANIC HARDWARE REQUIRED FOR A, E AND H
 OCCUPANCIES, FBC 1008.1.10.
  
  
  