| Plan Review Notes For Permit 16100788 |
| Permit Number |
16100788 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-27 17:39:44 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE | | | ROOFING ASSEMBLY THAT WILL BE INSTALLED ON THE FLAT | | | ROOF AS REQUIRED BY DCA RULE 9N-3. FBC 107.3.4 | | | | | | 2) SPECIFY THE APPROVED ASSEMBLY, THE FASTENING OPTION | | | AND THE DESIGN PRESSURE. IF THE PRODUCT APPROVAL | | | REQUIRES ENHANCED FASTENING FOR THE PERIMETER AND | | | CORNER AREAS, PROVIDE SIGNED AND SEALED RAS117 | | | CALCULATIONS. FBC 107.2.1.3 | | | |
|