| Plan Review Notes For Permit 16100741 |
| Permit Number |
16100741 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-09 17:36:30 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO'S (REVISION REQUIRED) | | | | | | 1] CORRECT NOTE 2 TYPO TO "TAMPER RESISTANT". | | | 2] CORRECT LOAD DEMAND OF 210 AMPS TO MATCH PANEL | | | SCHEDULE. | | | 3] ILLUMINATION REQUIRED FOR PANEL DEDICATED WORK SPACE | | | PER NEC 110.26(D). | | | 4] GFCI PROTECTION REQUIRED FOR KITCHEN COUNTER-TOP | | | RECEPTACLES PER NEC 210.8(A)(6) | | | 5] SMALL APPLIANCE CIRCUITS SHALL BE A MINIMUM OF 20 | | | AMP WITH 12 AWG WIRE PER NEC 210.52(B)(4). | | | |
|