| 2016-11-02 09:48:19 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - THE PLANS SUBMMITTED DON'T CONTAIN ANY ELECTRICAL | | | DETAILS, THE ONLY ELECTRICAL INFORMATION IS A NOTE FOR | | | AN EXISTING 20 AMP DISCONNECT WHICH COMPLIES WITH NEC | | | 600.6. BELOW FIND A LIST OF ITEMS REQUIRED. | | | | | | 1] PROVIDE A ELECTRICAL PLAN TO INCLUDE MINIMUM A 20 | | | AMP DEDICATED CIRCUIT FOR THE SIGN PER NEC 600.5 | | | | | | 2] ADD A BLOCK NOTE FOR ALL GROUNDING AND BONDING TO | | | COMPLY WITH NEC 600.7 | | | | | | 3] LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF | | | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS | | | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC-E | | | SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS (SHOW | | | COMPLIANCE) | | | | | | 4] THE PERMIT VALUATION AND PERMIT FEE MUST | | | COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED | | | CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION | | | ACCORDINGLY AND SHOW PROOF WITH AN OWNER SIGNED | | | CONTRACT. FBC- 109.3 | | | | | | |
|