| Plan Review Notes For Permit 16100726 |
| Permit Number |
16100726 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-03 11:15:56 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PLEASE CLARIFY THE ELECTRICAL SCOPE OF WORK. IF | | | RUNING NEW CICUITS SHOW A SMALL ONE LINE DIAGRAM | | | REFLECTING CONDUCTOR AND RACEWAY ROUTING PLUS A PANEL | | | SCHEDULE IDENTIFYING CIRCUIT # WITH OVERCURRENT | | | PROTECTION AMPERE RATING. | | | | | | 2] PROVIDE MANUFACTURE SPECIFICATIONS INDICATING | | | NAMEPLATE RATING OF EQUIPMENT IDENTIFYING MINIMUM | | | AMPERE RATING AND MAXIMUM OVERCURRENT DEVICE PER NEC | | | 440. |
|