| Plan Review Notes For Permit 16100709 |
| Permit Number |
16100709 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-09 12:56:23 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. PIPING TO FIRST TEE AT TANKLESS WATER HEATERS SHALL | | | BE 1". PER FBC FGC TABLE 402(5) AND 402.4.1 | | | | | | 2.THE SECTION OF PIPE BETWEEN THE RANGE AND THE POOL | | | HEATER SHALL BE 1". PER FBC FGC TABLE 402(22) AND | | | 402.4.1 | | | | | | 3. THE UNDER GROUND PIPING CAN NOT BE SCH 40 METALLIC | | | THE SLEEVE WOULD NOT BE WATER TIGHT THE WAY IT WOULD BE | | | ASSEMBLED. THE TRAC PIPE PS-11 CAN BE USED WITH NO | | | SLEEVE IF INSTALLED PER MANUFACTURE INSTILLATION GUIDE. | | | PER FBC FG 404.11 | | | | | | 4. THE PE PIPE TO THE FIRE PIT ON POOL DECK CAN NOT RUN | | | UNDER COVERED TERRACE IT SHALL RUN UNDER OPEN WALKWAY | | | BETWEEN TERRACE AND THE GYM. FBC FG 404.17.1 EXCEPTION | | | 3. | | | | | | 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | |
|