Plan Review Notes
Plan Review Notes For Permit 16100694
Permit Number 16100694
Review Stop M
Sequence Number 2
Notes
Date Text
2016-12-19 14:13:30PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENERGY FORM R405-2014 THAT WAAS SUBMITTED IS NOT
 ACCEPTABLE. FBC ENERGY CONSERVATION SECTION
 R101.5.1.1.2 AND R103.1.1.2
 - THE LOCATION ON THE FORM SHOULD BE WEST PALM BEACH
 NOT OKEECHOBEE.
 - THE OWNER AND BUILDER NAMES ARE MISSING FROM THE
 FORM.
 - THE CONSTRUCTION IS EXISTING WITH A NEW ADDITION, THE
 FORM STATES NEW CONSTRUCTION.
 - THIS IS SITE SPECIFIC AND CAN NOT BE WORST CASE. THE
 CORRECT ORIENTATION OF THE DWELLING IS REQUIRED TO BE
 USED FOR THE CALCULATIONS.
 - THE ROTATION ANGLE IS 0.
 - THERE ARE 3 BEDROOMS SO THE NUMBER OF OCCUPANTS
 SHOULD BE 6.
 - THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 R405-2014 FORM.
  
  
  