| 2016-12-19 14:13:30 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENERGY FORM R405-2014 THAT WAAS SUBMITTED IS NOT | | | ACCEPTABLE. FBC ENERGY CONSERVATION SECTION | | | R101.5.1.1.2 AND R103.1.1.2 | | | - THE LOCATION ON THE FORM SHOULD BE WEST PALM BEACH | | | NOT OKEECHOBEE. | | | - THE OWNER AND BUILDER NAMES ARE MISSING FROM THE | | | FORM. | | | - THE CONSTRUCTION IS EXISTING WITH A NEW ADDITION, THE | | | FORM STATES NEW CONSTRUCTION. | | | - THIS IS SITE SPECIFIC AND CAN NOT BE WORST CASE. THE | | | CORRECT ORIENTATION OF THE DWELLING IS REQUIRED TO BE | | | USED FOR THE CALCULATIONS. | | | - THE ROTATION ANGLE IS 0. | | | - THERE ARE 3 BEDROOMS SO THE NUMBER OF OCCUPANTS | | | SHOULD BE 6. | | | - THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | R405-2014 FORM. | | | | | | | | | |
|