| Notes |
| Date |
Text |
| 2016-12-06 08:42:20 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS TO SHOW THAT | | | EXISTING EQUIPMENT IS ADEQUATE FOR ADDITIONAL SPACE. | | | | | | 2) THE ENERGY FORM R402 IS NOT COMPLETELY FILLED OUT | | | AND THE OWNER/AGENT SIGNATURE IS MISSING. FBC ENERGY | | | R103.1.1.2 AND R402.1 | | | | | | 3) THE ATTIC INSULATION ON THE WALL SECTION ON SHEET | | | D-1 SHOWS R-19 CEILING INSULATION AND R-30 IS REQUIRED | | | WHEN THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC | | | ENERGY R402.1 | | | | | | 4) THE A/C SUPPLY DUCTS THAT ARE LOCATED IN THE ATTIC | | | ARE REQUIRED TO BE INSULATED TO A MINIMUM OF R-8 WHEN | | | THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC | | | ENERGY R403.2.1 | | | |
|