2016-12-06 08:42:20PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS TO SHOW THAT
 EXISTING EQUIPMENT IS ADEQUATE FOR ADDITIONAL SPACE.
  
 2) THE ENERGY FORM R402 IS NOT COMPLETELY FILLED OUT
 AND THE OWNER/AGENT SIGNATURE IS MISSING. FBC ENERGY
 R103.1.1.2 AND R402.1
  
 3) THE ATTIC INSULATION ON THE WALL SECTION ON SHEET
 D-1 SHOWS R-19 CEILING INSULATION AND R-30 IS REQUIRED
 WHEN THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC
 ENERGY R402.1
  
 4) THE A/C SUPPLY DUCTS THAT ARE LOCATED IN THE ATTIC
 ARE REQUIRED TO BE INSULATED TO A MINIMUM OF R-8 WHEN
 THE PRESCRIPTIVE METHOD OF COMPLIANCE IS USED. FBC
 ENERGY R403.2.1
  