| 2016-12-06 11:02:11 | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SPECIFY THE ROOF SLOPE ON THE PLANS. FBC R902 |
| | |
| | 2) SHEET D-1 IS TITLED A PROPOSED GARAGE. CORRECTION |
| | REQUIRED. FBC 107.2.1 |
| | |
| | 3) THE NOTE ON THE WALL SECTION ON SHEET D-1 SPECIFIES |
| | THE SOFFIT VENTS AT 6 INCHES (6") ON CENTER. PLEASE |
| | CLARIFY. FBC R806 |
| | |
| | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| | THE ROOFING MATERIALS, WINDOW/GLASS TYPES, AND EXTERIOR |
| | DOOR TYPES. |
| | |
| | 5) FBC - R301.2.1.2 PROTECTION OF OPENINGS. GLAZED |
| | OPENINGS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| | REGIONS SHALL BE PROTECTED FROM WINDBORNE DEBRIS. |
| | GLAZED OPENING PROTECTION FOR WINDBORNE DEBRIS SHALL |
| | MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM |
| | E 1996 AND ASTM E 1886 REFERENCED THEREIN, SSTD 12, TAS |
| | 201, 202 AND 203 OR AAMA 506, AS APPLICABLE. |
| | |
| | 6) GENERAL NOTE 10 ON D-1 INCORRECTLY SPECIFIES ACI 318 |
| | - 05. THE 2011 EDITION OF ACI 318 IS REFERENCED IN THE |
| | 2014 FBC. |
| | |
| | 7) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |