| Plan Review Notes For Permit 16100664 |
| Permit Number |
16100664 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-03-17 12:58:48 | MECHANICAL PROVISOS: | | | 3/17/17 | | | | | | THE PLANS ARE APPROVED WITH THE FOLLOWING LIST OF | | | PROVISOS: | | | | | | 1) SUBMIT STRUCTURAL DETAILS FOR THE COOLING TOWER | | | ACCESS PLATFORM AND PERMANENT LADDER. | | | | | | 2) SUBMIT CHILLED WATER PIPING AND PIPING INSULATION | | | SPECIFICATIONS. | | | | | | 3) COMPLY WITH THE FBC-14 ACCESSIBILTY CODE FOR | | | LOCATING THE TEMPORARY COOLING TOWER AND EQUIPMENT IN | | | THE PARKING LOT- THE LOCATION OF THE EQUIPMENT SHALL | | | NOT REDUCE THE NUMBER OF REQUIRED ACESSIBILE PARKING | | | SPACES. | | | | | | 4) SUBMIT BOTH PRELIMINARY AND FINAL COMMISSIONING | | | REPORTS | | | | | | .CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|