2017-03-17 12:58:48MECHANICAL PROVISOS:
 3/17/17
  
 THE PLANS ARE APPROVED WITH THE FOLLOWING LIST OF
 PROVISOS:
  
 1) SUBMIT STRUCTURAL DETAILS FOR THE COOLING TOWER
 ACCESS PLATFORM AND PERMANENT LADDER.
  
 2) SUBMIT CHILLED WATER PIPING AND PIPING INSULATION
 SPECIFICATIONS.
  
 3) COMPLY WITH THE FBC-14 ACCESSIBILTY CODE FOR
 LOCATING THE TEMPORARY COOLING TOWER AND EQUIPMENT IN
 THE PARKING LOT- THE LOCATION OF THE EQUIPMENT SHALL
 NOT REDUCE THE NUMBER OF REQUIRED ACESSIBILE PARKING
 SPACES.
  
 4) SUBMIT BOTH PRELIMINARY AND FINAL COMMISSIONING
 REPORTS
  