| Plan Review Notes For Permit 16100664 |
| Permit Number |
16100664 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-16 09:35:25 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100664 | | | 12/16/16 | | | | | | 1) IN REFERENCE TO 1ST REVIEW COMMENT #6, PLEASE | | | PROVIDE STRUCTURAL DETAILS FOR THE NEW COOLING TOWER | | | PLATFORM, GUARDRAILS, AND PERMANENT LADDER- SEE | | | SECTIONS 304.11 AND 306.5 MECHANICAL, AND SECTION | | | 1509.6.4 FBC-14 BUILDING: THE LADDER SHALL EXTEND FROM | | | THE ROOF SURFACE TO THE PLATFORM AND NOT REQUIRE THE | | | USE OF A PORTABLE LADDER.- SEE THE NOTE FOR LADDER | | | EXTENSION ON SHEET M002. | | | | | | 2) IN REFERENCE TO 1ST REVIEW COMMENT #7, SHOW THE | | | CLEARANCE DISTANCE MEASUREMENTS FROM THE RETURN | | | DUCTWORK OF RTU-4 & 5 TO THE ROOF EDGES. | | | | | | 3) IN REFERENCE TO 1ST REVIEW COMMENT #9, SHOW THE | | | ROOFTOP CONDENSATE PIPING RUNS AND SUPPORT AND | | | PROTECTION DETAILS. | | | | | | 4) PLEASE PROVIDE A SITE PLAN SHOWING THE EXACT | | | LOCATIONS OF THE TEMPORARY COOLING TOWERS, GENERATORS | | | ETC.AND HOW THE EQUIPMENT WILL BE PROTECTED AGAINST | | | DAMAGE- SECTION 303.4 | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|