| 2017-04-07 09:38:17 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100663 | | | 4/7/16 | | | | | | 1) THE SUBMITTED LETTERS FROM MW/DAVIS DUMAS & | | | ASSOCIATES, INC. JIMMY JEFFCOAT PE FROM TRANE, ALONG | | | WITH THE DATA REPORTS FOR THE CONDENSERS AND COILS ARE | | | NOT INDICATING THAT THE THE TWO COMPONENTS OF THE | | | PROPOSED DX SYSTEM- NEW TRANE CONDENSERS PAIRED WITH | | | THE NEW TRANE AHU COILS- WILL MEET THE EFFICIENCY | | | RATING WHEN TESTED IN ACCORDANCE WITH AHRI 340/360- SEE | | | | | | TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. IN | | | ACCORDANCE WITH SECTION C101.4.7 THE MATCHING OF THE | | | PROPOSED SYSTEM COMPONENTS CAN BE VERIFIED BY AHRI | | | DATA, HOWEVER THE DATA SUBMITTED IS VERYING COMPLIANCE | | | FOR EACH COMPONENT INDIVIDUALLY - THE CONDENSERS UNDER | | | AHRI 365, AND THE COILS UNDER AHRI 410. I AM NOT SEEING | | | ANY DATA OR LANGUAGE IN EITHER OF THE LETTERS | | | | | | THAT STATES SPECIFICALLY THAT THE TWO COMPONENTS | | | FUNCTIONING TOGETHER WILL MEET OR EXCEED THE EFFIENCIES | | | REQUIRED BYTABLE C403.2.3(1). | | | | | | ADDITIONALLY, PLEASE NOTE THAT THE LETTER FROM JIMMY | | | JEFFCOAT PE REQUIRES AN ORIGNIAL SIGNATURE AND SEAL PER | | | SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|