Plan Review Notes
Plan Review Notes For Permit 16100663
Permit Number 16100663
Review Stop M
Sequence Number 4
Notes
Date Text
2017-04-07 09:38:174TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16100663
 4/7/16
  
 1) THE SUBMITTED LETTERS FROM MW/DAVIS DUMAS &
 ASSOCIATES, INC. JIMMY JEFFCOAT PE FROM TRANE, ALONG
 WITH THE DATA REPORTS FOR THE CONDENSERS AND COILS ARE
 NOT INDICATING THAT THE THE TWO COMPONENTS OF THE
 PROPOSED DX SYSTEM- NEW TRANE CONDENSERS PAIRED WITH
 THE NEW TRANE AHU COILS- WILL MEET THE EFFICIENCY
 RATING WHEN TESTED IN ACCORDANCE WITH AHRI 340/360- SEE
  
 TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. IN
 ACCORDANCE WITH SECTION C101.4.7 THE MATCHING OF THE
 PROPOSED SYSTEM COMPONENTS CAN BE VERIFIED BY AHRI
 DATA, HOWEVER THE DATA SUBMITTED IS VERYING COMPLIANCE
 FOR EACH COMPONENT INDIVIDUALLY - THE CONDENSERS UNDER
 AHRI 365, AND THE COILS UNDER AHRI 410. I AM NOT SEEING
 ANY DATA OR LANGUAGE IN EITHER OF THE LETTERS
  
 THAT STATES SPECIFICALLY THAT THE TWO COMPONENTS
 FUNCTIONING TOGETHER WILL MEET OR EXCEED THE EFFIENCIES
 REQUIRED BYTABLE C403.2.3(1).
  
 ADDITIONALLY, PLEASE NOTE THAT THE LETTER FROM JIMMY
 JEFFCOAT PE REQUIRES AN ORIGNIAL SIGNATURE AND SEAL PER
 SECTION 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  