Plan Review Notes
Plan Review Notes For Permit 16100663
Permit Number 16100663
Review Stop M
Sequence Number 3
Notes
Date Text
2017-03-24 12:06:073RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16100663
 3/24/17
  
 1) THE REQUESTED DOCUMENTATION OF AHRI CERTIFICATION
 FOR THE REPLACED AC SYSTEMS HAS NOT BEEN PROVIDED.
 PLEASE SEE EXCEPTION #2 PRINTED BELOW
  
 SECTION C101.4.7 FBC-14 ENERGY CONSERVATION: BUILDING
 SYSTEMS AND COMPONENTS.
 THERMAL EFFICIENCY STANDARDS ARE SET FOR THE FOLLOWING
 BUILDING SYSTEMS AND COMPONENTS WHERE NEW PRODUCTS ARE
 INSTALLED OR REPLACED IN EXISTING BUILDINGS, AND FOR
 WHICH A PERMIT MUST BE OBTAINED. NEW PRODUCTS SHALL
 MEET THE MINIMUM EFFICIENCIES ALLOWED BY THIS CODE FOR
 THE FOLLOWING SYSTEMS AND COMPONENTS:
  
 HEATING, VENTILATING OR AIR CONDITIONING SYSTEMS.
  
 SERVICE WATER OR POOL HEATING SYSTEMS.
  
 ELECTRICAL SYSTEMS AND MOTORS.
  
 LIGHTING SYSTEMS.
  
 REPLACEMENT FENESTRATION.
  
 EXCEPTIONS:
  
 1. WHERE PART OF A FUNCTIONAL UNIT IS REPAIRED OR
 REPLACED. FOR EXAMPLE, REPLACEMENT OF AN ENTIRE HVAC
 SYSTEM IS NOT REQUIRED BECAUSE A NEW COMPRESSOR OR
 OTHER PART DOES NOT MEET CODE WHEN INSTALLED WITH AN
 OLDER SYSTEM.
  
 2. IF THE UNIT BEING REPLACED IS ITSELF A FUNCTIONAL
 UNIT, SUCH AS A CONDENSER, IT DOES NOT CONSTITUTE A
 REPAIR. OUTDOOR AND INDOOR UNITS THAT ARE NOT DESIGNED
 TO BE OPERATED TOGETHER MUST MEET THE U.S. DEPARTMENT
 OF ENERGY CERTIFICATION REQUIREMENTS CONTAINED IN
 SECTION C403.2.3. MATCHED SYSTEMS ARE REQUIRED; THIS
 MATCH MAY BE VERIFIED BY ANY ONE OF THE FOLLOWING
 MEANS:
  
 A. AHRI DATA.
  
 B. ACCREDITED LABORATORY.
  
 C. MANUFACTURER'S LETTER.
  
 D. LETTER FROM REGISTERED PROFESSIONAL ENGINEER (P.E.),
 STATE OF FLORIDA.
  
 3. WHERE EXISTING COMPONENTS ARE UTILIZED WITH A
 REPLACEMENT SYSTEM, SUCH AS AIR DISTRIBUTION SYSTEM
 DUCTS OR ELECTRICAL WIRING FOR LIGHTS, SUCH COMPONENTS
 OR CONTROLS NEED NOT MEET CODE IF MEETING CODE WOULD
 REQUIRE THAT COMPONENT?S REPLACEMENT.
  
 4. REPLACEMENT EQUIPMENT THAT WOULD REQUIRE EXTENSIVE
 REVISIONS TO OTHER SYSTEMS, EQUIPMENT OR ELEMENTS OF A
 BUILDING WHERE SUCH REPLACEMENT IS A LIKE-FOR-LIKE
 REPLACEMENT, SUCH AS THROUGH-THE-WALL CONDENSING UNITS
 AND PTACS, CHILLERS, AND COOLING TOWERS IN CONFINED
 SPACES.
  