| Plan Review Notes For Permit 16100663 |
| Permit Number |
16100663 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-12-13 17:20:17 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100663 | | | 12/13/16 | | | | | | 1) PROVIDE AHRI CERTIFCATION FOR THE REPLACED SYSTEMS- | | | SECTION C101.4.7 FBC-14 ENERGY CONSERVATION. | | | | | | 2) IN REFERENCE TO COMMENT #6 FROM THE 1ST REVIEW, | | | VERIFY THE SCREEN WALLS, WHICH ARE ALSO CONSIDERED | | | GUARDS, HAVE ADEQUATE STRENGTH AND ATTACHMENT PER | | | SECTION 1607.8 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|