2016-10-31 10:10:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED
 IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN
 SHOWING LOCATION OF PROPOSED IMPROVEMENT.
  
 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY
 COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED
 BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN
 "LICENSE").
  
 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN
 THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN
 CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND
 SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL
 COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE
 COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA
 BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD
 WITH A COPY OF A CERTIFICATE OF COMPLETION,
 FAC61G15-22.001.
  
 THE WEBSITE HAS NOT BEEN UPDATED TO REFLECT THAT MR.
 COOKE AND MR. DAVIS HAVE TAKEN THE COURSE. CONTACT FBPE
 FOR MORE INFORMATION.
  
 4. THE TITLE BLOCK FOR THE ENGINEERS IS LACKING THE
 CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM,
 PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL
 SIGNING AND SEALING THE PLAN.
  
 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE
 BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE,
 OCCUPANCY CLASSIFICATION.
  
 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO
 BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL,
 FBC 107.
  
 7. FOR THE ROOF COVERING, INDICATE THE APPROVED
 ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF
 APPLICABLE.
  
 CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO
 ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED.
 THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE
 SUBMITTED AS A REVISION.
  
 8. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. (THIS IS REQUIRED FOR BOTH A SHEETS AND S
 SHEETS.)
  
 9. METHOD OF MOUNTING OF EQUIPMENT NOT CLEAR, PROVIDE A
 DETAIL, FBC 107, FBC 1609. IF USING A STAND, PROVIDE
 THE PRODUCT APPROVAL. ON THE PRODUCT APPROVAL, INDICATE
 THE INSTALLATION PROPOSED. NOTE THAT NO STRUCTURAL
 DRAWINGS WERE SUBMITTED. WHEN RESUBMITTING, SHOW
 COMPLIANCE WITH FBC TABLE 1509.6.5 IF APPLICABLE.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  