| 2016-10-31 10:10:42 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SEE NFIP REVIEW. A PORTION OF THIS PARCEL IS LOCATED |
| | IN A SPECIAL FLOOD HAZARD AREA. PROVIDE A SITE PLAN |
| | SHOWING LOCATION OF PROPOSED IMPROVEMENT. |
| | |
| | 2. FAC61G15-23, THE SEAL USED BY ENGINEERS TIMOTHY |
| | COOKE, PE AND JAMES SAMUEL DAVIS, PE IS NOT PERMITTED |
| | BY FBPE (SEAL STATES "CERTIFICATE" RATHER THAN |
| | "LICENSE"). |
| | |
| | 3. ALL (ENGINEER) LICENSEES ACTIVELY PARTICIPATING IN |
| | THE DESIGN OF ENGINEERING WORKS OR SYSTEMS IN |
| | CONNECTION WITH BUILDING, STRUCTURES, OR FACILITIES AND |
| | SYSTEMS COVERED BY THE FLORIDA BUILDING CODE SHALL |
| | COMPLETE AT LEAST ONE ADVANCED FLORIDA BUILDING CODE |
| | COURSE WITHIN 12 MONTHS OF EACH EDITION OF THE FLORIDA |
| | BUILDING CODE EFFECTIVE DATE, AND PROVIDE THE BOARD |
| | WITH A COPY OF A CERTIFICATE OF COMPLETION, |
| | FAC61G15-22.001. |
| | |
| | THE WEBSITE HAS NOT BEEN UPDATED TO REFLECT THAT MR. |
| | COOKE AND MR. DAVIS HAVE TAKEN THE COURSE. CONTACT FBPE |
| | FOR MORE INFORMATION. |
| | |
| | 4. THE TITLE BLOCK FOR THE ENGINEERS IS LACKING THE |
| | CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING FIRM, |
| | PRINTED NAME AND LICENSE NUMBER OF THE INDIVIDUAL |
| | SIGNING AND SEALING THE PLAN. |
| | |
| | 5. REVISE PLAN TO INCLUDE INFORMATION REGARDING THE |
| | BUILDING - BUILDING TYPE, FBC CHAPTER 6, SIZE, |
| | OCCUPANCY CLASSIFICATION. |
| | |
| | 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | ROOF COVERING, EIFS, FBC 1609. PRODUCT APPROVALS ARE TO |
| | BE REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, |
| | FBC 107. |
| | |
| | 7. FOR THE ROOF COVERING, INDICATE THE APPROVED |
| | ASSEMBLY PROPOSED AND PROVIDE ENGINEERING IF |
| | APPLICABLE. |
| | |
| | CONTRACTOR MAY ELECT TO DEFER THIS SUBMITTAL. PRIOR TO |
| | ROOF INSTALLATION, A SEPARATE ROOF PERMIT IS REQUIRED. |
| | THE PRODUCT APPROVAL AND ENGINEERING ARE TO BE |
| | SUBMITTED AS A REVISION. |
| | |
| | 8. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA FBC |
| | 1603.1.4. (THIS IS REQUIRED FOR BOTH A SHEETS AND S |
| | SHEETS.) |
| | |
| | 9. METHOD OF MOUNTING OF EQUIPMENT NOT CLEAR, PROVIDE A |
| | DETAIL, FBC 107, FBC 1609. IF USING A STAND, PROVIDE |
| | THE PRODUCT APPROVAL. ON THE PRODUCT APPROVAL, INDICATE |
| | THE INSTALLATION PROPOSED. NOTE THAT NO STRUCTURAL |
| | DRAWINGS WERE SUBMITTED. WHEN RESUBMITTING, SHOW |
| | COMPLIANCE WITH FBC TABLE 1509.6.5 IF APPLICABLE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |