Plan Review Notes
Plan Review Notes For Permit 16100661
Permit Number 16100661
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-16 08:28:13BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
 1. PLANS APPEAR TO BE THE WORK PRODUCT OF A LICENSED
 ARCHITECT. DESIGNER OF RECORD TO SIGN AND SEAL PLANS
 PER FS 481.
 2. REMOVE INFORMATION ON PLANS THAT DOES NOT PERTAIN TO
 SCOPE OF WORK.
 3. GOVERNING CODES STATED ON PLANS ARE UNENFORCEABLE.
 STATE CURRENT GOVERNING CODES ON PLANS.
 4. PLANS INDICATE A GRADE BEAM WILL BE INSTALLED.
 PROVIDE STRUCTURAL DETAIL REVIEWED AND APPROVED BY
 DESIGNER.
 5. DESIGNER OR OWNER TO STATE CATERGORY OF SUNROOM
 BEING CONSTRUCTED.
 6. PROVIDE DEMENSIONS OF ROUGH OPENINGS.
 7. PROVIDE DESIGN WIND LOADS FOR OPENINGS.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 R301.2.1.1.2.2
 FOR THE PURPOSE OF APPLYING THE CRITERIA OF THE
 AAMA/NPEA/NSA 2100, SUNROOMS SHALL BE CATEGORIZED IN
 ONE OF THE FOLLOWING CATEGORIES BY THE PERMIT
 APPLICANT, DESIGN PROFESSIONAL OR THE PROPERTY OWNER
 WHERE THE SUNROOM IS BEING CONSTRUCTED.
  
 CATEGORY I: A THERMALLY ISOLATED SUNROOM WITH WALLS
 THAT ARE EITHER OPEN OR ENCLOSED WITH INSECT SCREENING
 OR 0.5 MM (20 MIL) MAXIMUM THICKNESS PLASTIC FILM. THE
 SPACE IS DEFINED AS A NONHABITABLE, NONCONDITIONED
 SUNROOM.
  
 CATEGORY II: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED
 WALLS. THE OPENINGS ARE PERMITTED TO BE ENCLOSED WITH
 TRANSLUCENT OR TRANSPARENT PLASTIC OR GLASS. THE SPACE
 IS DEFINED AS A NONHABITABLE, NONCONDITIONED SUNROOM.
  
 CATEGORY III: A THERMALLY ISOLATED SUNROOM WITH
 ENCLOSED WALLS. THE OPENINGS ARE PERMITTED TO BE
 ENCLOSED WITH TRANSLUCENT OR TRANSPARENT PLASTIC OR
 GLASS. THE SUNROOM FENESTRATION COMPLIES WITH
 ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION RESISTANCE
 AND WATER PENETRATION RESISTANCE. THE SPACE IS DEFINED
 AS A NONHABITABLE, NONCONDITIONED SUNROOM.
  
 CATEGORY IV: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED
 WALLS. THE SUNROOM IS DESIGNED TO BE HEATED AND/OR
 COOLED BY A SEPARATE TEMPERATURE CONTROL OR SYSTEM AND
 IS THERMALLY ISOLATED FROM THE PRIMARY STRUCTURE. THE
 SUNROOM FENESTRATION COMPLIES WITH ADDITIONAL
 REQUIREMENTS FOR AIR INFILTRATION RESISTANCE, WATER
 PENETRATION RESISTANCE, AND THERMAL PERFORMANCE. THE
 SPACE IS DEFINED AS A NONHABITABLE AND CONDITIONED
 SUNROOM.
  
 CATEGORY V: A SUNROOM WITH ENCLOSED WALLS. THE SUNROOM
 IS DESIGNED TO BE HEATED AND/OR COOLED AND IS OPEN TO
 THE MAIN STRUCTURE. THE SUNROOM FENESTRATION COMPLIES
 WITH ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION
 RESISTANCE, WATER PENETRATION RESISTANCE, AND THERMAL
 PERFORMANCE. THE SPACE IS DEFINED AS A HABITABLE AND
 CONDITIONED SUNROOM.
  
 R301.2.1.1.2.1
 SUNROOMS SHALL COMPLY WITH AAMA/NPEA/NSA 2100 AS
 MODIFIED BELOW.
  
 AAMA 2100, SECTION 5.2.1 WIND LOADS: MODIFY SECTION
 5.2.1 AS FOLLOWS:
  
 5.2.1 WIND LOADS: BASIC WIND SPEED (VASD) IN MILES PER
 HOUR (MPH) SHALL BE DETERMINED IN ACCORDANCE WITH
 SECTION R301.2.1. SUNROOMS INCLUDING EXPOSED
 STRUCTURES, COMPONENTS, CLADDING, AND ROOF COVERING
 SHALL BE DESIGNED TO RESIST THE WIND LOADS AS
 ESTABLISHED IN SECTION R301.2.1.
  
 R606.16 MASONRY OPENING TOLERANCES.
 MASONRY ROUGH OPENINGS MAY VARY IN THE CROSS SECTION
 DIMENSION OR ELEVATION DIMENSION SPECIFIED ON THE
 APPROVED PLANS FROM - 1/4 INCHES (6.4 MM) TO + 1/2
 INCHES (12.7 MM). FOR EXTERIOR WINDOW AND DOOR
 INSTALLATION PROVISIONS, SEE SECTIONS R612.3 AND
 R612.10.
  
 R612.8.4 MASONRY ROUGH OPENINGS.
 MASONRY ROUGH OPENING DIMENSIONS SHALL BE WITHIN THE
 TOLERANCES SPECIFIED AT SECTION R606.16 AND, IN
 ADDITION, SHALL PROVIDE FOR A WINDOW PERIMETER SEALANT
 JOINT A MAXIMUM OF 1/4 INCHES (6.4 MM) IN WIDTH.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED UPON CORRECTION AND
 RE-SUBMITTAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  