| 2016-11-16 08:28:13 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | |
| | 1. PLANS APPEAR TO BE THE WORK PRODUCT OF A LICENSED |
| | ARCHITECT. DESIGNER OF RECORD TO SIGN AND SEAL PLANS |
| | PER FS 481. |
| | 2. REMOVE INFORMATION ON PLANS THAT DOES NOT PERTAIN TO |
| | SCOPE OF WORK. |
| | 3. GOVERNING CODES STATED ON PLANS ARE UNENFORCEABLE. |
| | STATE CURRENT GOVERNING CODES ON PLANS. |
| | 4. PLANS INDICATE A GRADE BEAM WILL BE INSTALLED. |
| | PROVIDE STRUCTURAL DETAIL REVIEWED AND APPROVED BY |
| | DESIGNER. |
| | 5. DESIGNER OR OWNER TO STATE CATERGORY OF SUNROOM |
| | BEING CONSTRUCTED. |
| | 6. PROVIDE DEMENSIONS OF ROUGH OPENINGS. |
| | 7. PROVIDE DESIGN WIND LOADS FOR OPENINGS. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | R301.2.1.1.2.2 |
| | FOR THE PURPOSE OF APPLYING THE CRITERIA OF THE |
| | AAMA/NPEA/NSA 2100, SUNROOMS SHALL BE CATEGORIZED IN |
| | ONE OF THE FOLLOWING CATEGORIES BY THE PERMIT |
| | APPLICANT, DESIGN PROFESSIONAL OR THE PROPERTY OWNER |
| | WHERE THE SUNROOM IS BEING CONSTRUCTED. |
| | |
| | CATEGORY I: A THERMALLY ISOLATED SUNROOM WITH WALLS |
| | THAT ARE EITHER OPEN OR ENCLOSED WITH INSECT SCREENING |
| | OR 0.5 MM (20 MIL) MAXIMUM THICKNESS PLASTIC FILM. THE |
| | SPACE IS DEFINED AS A NONHABITABLE, NONCONDITIONED |
| | SUNROOM. |
| | |
| | CATEGORY II: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED |
| | WALLS. THE OPENINGS ARE PERMITTED TO BE ENCLOSED WITH |
| | TRANSLUCENT OR TRANSPARENT PLASTIC OR GLASS. THE SPACE |
| | IS DEFINED AS A NONHABITABLE, NONCONDITIONED SUNROOM. |
| | |
| | CATEGORY III: A THERMALLY ISOLATED SUNROOM WITH |
| | ENCLOSED WALLS. THE OPENINGS ARE PERMITTED TO BE |
| | ENCLOSED WITH TRANSLUCENT OR TRANSPARENT PLASTIC OR |
| | GLASS. THE SUNROOM FENESTRATION COMPLIES WITH |
| | ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION RESISTANCE |
| | AND WATER PENETRATION RESISTANCE. THE SPACE IS DEFINED |
| | AS A NONHABITABLE, NONCONDITIONED SUNROOM. |
| | |
| | CATEGORY IV: A THERMALLY ISOLATED SUNROOM WITH ENCLOSED |
| | WALLS. THE SUNROOM IS DESIGNED TO BE HEATED AND/OR |
| | COOLED BY A SEPARATE TEMPERATURE CONTROL OR SYSTEM AND |
| | IS THERMALLY ISOLATED FROM THE PRIMARY STRUCTURE. THE |
| | SUNROOM FENESTRATION COMPLIES WITH ADDITIONAL |
| | REQUIREMENTS FOR AIR INFILTRATION RESISTANCE, WATER |
| | PENETRATION RESISTANCE, AND THERMAL PERFORMANCE. THE |
| | SPACE IS DEFINED AS A NONHABITABLE AND CONDITIONED |
| | SUNROOM. |
| | |
| | CATEGORY V: A SUNROOM WITH ENCLOSED WALLS. THE SUNROOM |
| | IS DESIGNED TO BE HEATED AND/OR COOLED AND IS OPEN TO |
| | THE MAIN STRUCTURE. THE SUNROOM FENESTRATION COMPLIES |
| | WITH ADDITIONAL REQUIREMENTS FOR AIR INFILTRATION |
| | RESISTANCE, WATER PENETRATION RESISTANCE, AND THERMAL |
| | PERFORMANCE. THE SPACE IS DEFINED AS A HABITABLE AND |
| | CONDITIONED SUNROOM. |
| | |
| | R301.2.1.1.2.1 |
| | SUNROOMS SHALL COMPLY WITH AAMA/NPEA/NSA 2100 AS |
| | MODIFIED BELOW. |
| | |
| | AAMA 2100, SECTION 5.2.1 WIND LOADS: MODIFY SECTION |
| | 5.2.1 AS FOLLOWS: |
| | |
| | 5.2.1 WIND LOADS: BASIC WIND SPEED (VASD) IN MILES PER |
| | HOUR (MPH) SHALL BE DETERMINED IN ACCORDANCE WITH |
| | SECTION R301.2.1. SUNROOMS INCLUDING EXPOSED |
| | STRUCTURES, COMPONENTS, CLADDING, AND ROOF COVERING |
| | SHALL BE DESIGNED TO RESIST THE WIND LOADS AS |
| | ESTABLISHED IN SECTION R301.2.1. |
| | |
| | R606.16 MASONRY OPENING TOLERANCES. |
| | MASONRY ROUGH OPENINGS MAY VARY IN THE CROSS SECTION |
| | DIMENSION OR ELEVATION DIMENSION SPECIFIED ON THE |
| | APPROVED PLANS FROM - 1/4 INCHES (6.4 MM) TO + 1/2 |
| | INCHES (12.7 MM). FOR EXTERIOR WINDOW AND DOOR |
| | INSTALLATION PROVISIONS, SEE SECTIONS R612.3 AND |
| | R612.10. |
| | |
| | R612.8.4 MASONRY ROUGH OPENINGS. |
| | MASONRY ROUGH OPENING DIMENSIONS SHALL BE WITHIN THE |
| | TOLERANCES SPECIFIED AT SECTION R606.16 AND, IN |
| | ADDITION, SHALL PROVIDE FOR A WINDOW PERIMETER SEALANT |
| | JOINT A MAXIMUM OF 1/4 INCHES (6.4 MM) IN WIDTH. |
| | |
| | ADDITIONAL COMMENTS MAY BE PROVIDED UPON CORRECTION AND |
| | RE-SUBMITTAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |