| Plan Review Notes For Permit 16100655 |
| Permit Number |
16100655 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-31 09:08:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100665 | | | 10/31/16 | | | | | | 1) BARBER SHOPS ARE REQUIRED TO HAVE AN EXHAUST SYSTEM | | | WITH A DESIGN CAPACITY OF 0.5 CFM PER SF. - REFER TO | | | TABLE 403.3. PLEASE REVISE THE PLAN AND THE VENTILATION | | | CALCULATIONS. | | | | | | 2) PLEASE CLARIFY WHY AN EXHAUST FAN IS BEING INSTALLED | | | IN THE EMPLOYEE LOUNGE AND PROVIDE A SIZING | | | CALCULATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|