2016-11-07 09:15:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE ADD A SHOW WINDOW RECEPTACLE AND SHOW LOAD ON
 PANEL SCHEDULE. NEC 21-.62
 2. PROVIDE A NOTE TO INDICATE ALL 125V RECEPTACLES
 WITHIN 6FT OF SINKS TO BE GFCI PROTECTED, A NOTE WILL
 SUFFICENEC 210.8B
 3. ADDRESS MECHANICAL AND FIRE COMMENTS RELATED TO
 ELECTRICAL.