| Plan Review Notes For Permit 16100655 |
| Permit Number |
16100655 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-11-07 09:15:29 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE ADD A SHOW WINDOW RECEPTACLE AND SHOW LOAD ON | | | PANEL SCHEDULE. NEC 21-.62 | | | 2. PROVIDE A NOTE TO INDICATE ALL 125V RECEPTACLES | | | WITHIN 6FT OF SINKS TO BE GFCI PROTECTED, A NOTE WILL | | | SUFFICENEC 210.8B | | | 3. ADDRESS MECHANICAL AND FIRE COMMENTS RELATED TO | | | ELECTRICAL. | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|