| Plan Review Notes For Permit 16100639 |
| Permit Number |
16100639 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-31 11:47:06 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16100639 | | | 10/31/16 | | | | | | 1) M-1: REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING | | | CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR | | | ALL ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) M-2: PROVIDE THE WIND LOAD DESIGN CRITERIA AND | | | DESIGN PRESSURES ON THE PLAN- SEE SECTION 1609 FBC-14. | | | | | | 3) ADVISORY: IN REGARD TO THE SEPARATELY PERMITTED | | | KITCHEN HOOD AND EXHAUST SYSTEM REFER TO SECTION | | | 508.1.1 FBC-14 MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|