Plan Review Notes
Plan Review Notes For Permit 16100614
Permit Number 16100614
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-02 12:20:551ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100614
 11/2/16
  
 1) SUBMIT ENERGY CALCULATIONS AND AC COOLING AND
 HEATING CALCULATIONS.
  
 2) SHEET M4.02: THE 10X9 TRANSFER DUCT AT BEDROOM 2
 (AHU-1 SYSTEM) IS UNDERSIZED PER SECTION 601.5
 EXCEPTION 1.
  
 3) SHEET M501: MECHANICAL VENTILATION RATES CANNOT BE
 USED TO VERIFY COMPLIANCE WITH THE NATURAL VENTILATION
 REQUIREMENT FOR THE GARAGES. PLEASE REVIEW SECTIONS
 401.2 AND 402.2 AND PROVIDE THE CORRECT CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  