Plan Review Notes
Plan Review Notes For Permit 16100614
Permit Number 16100614
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-09 14:23:57BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16100614
 ADD: 7160 OKEECHOBEE BLVD. BLDG. # 2/ BLDG. TYPE: II
 CONT: ELEV8 CONSTRUCTION CO./ STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. NOV. 09/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING# 2. BUILDING TYPE II,
 NOT FOR THE SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) THE BUILDING OFFICIAL HAS APPROVED THE COST ANALYSIS
 AND REVIEWING THE DOCUMENTS. THE 4 SUB-PERMITS THAT ARE
 A NO COST IF THEY CAME IN AT THE TIME OF THE PRIME
 PERMIT ARE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING.
 IF THEY COME IN AFTER THE PRIME PERMIT WAS CREATED THEY
 ARE A $80.00 SUB-PERMIT, THE $80.00 IS AN
 ADMINISTRATIVE FEE.
 THE VALUE OF THE SUB-PERMITS WHERE THE VALUE OF THE
 PERMIT IS NOT COVERED UNDER THE PRIME PERMIT NEED TO BE
 DEDUCTED FROM THE $280,000.00 STATED UNDER BLDG. 2/
 TYPE II. NOTE, THE MEP AND ROOFING PERMITS, ARE
 SUB-PERMITS AND IF NOT SUBMITTED AT THE TIME OF PERMIT
 ARE A $80.00 SUB-PERMIT AND ARE INCLUDED IN THE VALUE
 OF THE BUILDING COST. AN ITEMIZED LIST OF SUB-PERMITS
 NOT COVERED UNDER THE MASTER AND THE COST OF WORK
 ASSOCIATED WITH THEM NEEDS TO BE SUBMITTED TO THE CITY
 FOR REVIEW SO WE CAN REDUCE THE OVERALL BUILDING VALUE
 SO WE DO NOT CHARGE YOU TWICE FOR ASSOCIATED PERMIT
 FEES. PROVIDE AN ITEMIZED LIST.
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 2) THIS BUILDING IS A THRESHOLD BUILDING AND ADDENDUM
 TO THE THRESHOLD DOCUMENTS NEEDS TO OCCUR PROVIDING THE
 BUILDING ADDRESS AND PERMIT NUMBERS IF APPLICABLE FROM
 THE THRESHOLD INSPECTION COMPANY ACKNOWLEDGING THE
 ENLARGED SCOPE OF WORK. IF THERE IS ANY CHANGE IN THE
 ONSITE INSPECTORS OR ADDITIONAL INSPECTORS THEIR
 SIGNATURES ON THE APPROPRIATE FORMS WILL ALSO BE
 REQUIRED. WE WOULD ALSO NEED CURRENT LICENSURE FOR THE
 NEW JOBSITE INSPECTOR AND RESUME TO BE REVIEWED AND
 APPROVED BY THE CITY. THRESHOLD BUILDING / FL S. S.
 553.71(7) ?THRESHOLD BUILDING?.
  
  
 3A) IN THIS SUBMITTAL THE PLANS INDICATE THERE IS TO BE
 AN R-13 FIRE SPRINKLER SYSTEM. THERE IS NO HYDRAULIC
 CALCULATIONS SUBMITTED NOR PLANS FOR FIRE SPRINKLER
 LAYOUT PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 2014 FBC-B 903.2.11.3 BUILDINGS THREE STORIES OR MORE
 IN HEIGHT.
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1.
  
  
 3B) NO ACTION REQUIRED. ORIGINAL PAPER SIGNED AND
 SEALED SOILS REPORT FOR THE PROJECT IS FILED WITH THE
 RECREATION BUILDING PERMIT # 16020377.
  
 4) 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE
 SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY
 THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
  
 5A-5E) BUILDING PROVISO: PRODUCT APPROVALS TO BE
 DEFERRED SUBMITTALS.
  
 5B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING .
  
 5E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO
 RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA
 ARCHITECT OR ENGINEER.
 5F) COMPLIED. A/C STANDS.
  
 6) BUILDING PROVISO/ DEFERRED SUBMITTAL:
  
 6A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO
 FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 6B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS
 WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON
 SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED
 STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B
 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 6C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE
 REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING
 MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF
 ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 7) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & E5.01
 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 8) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved