| Plan Review Notes For Permit 16100611 |
| Permit Number |
16100611 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-28 15:17:57 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100611 | | | 11/28/16 | | | | | | 1) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. I AM | | | REPRINTING IT BELOW- PLEASE COMPLY. | | | | | | 2) SHEET M501: MECHANICAL VENTILATION RATES CANNOT BE | | | USED TO VERIFY COMPLIANCE WITH THE NATURAL VENTILATION | | | REQUIREMENT FOR THE GARAGES. PLEASE REVIEW SECTIONS | | | 401.2 AND 402.2 AND PROVIDE THE CORRECT CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|