| 2016-11-22 14:07:50 | FIRE SPRINKLER PERMIT #16110749 |
| | |
| | PROVISOS: |
| | |
| | 1) BUILDING PROVISO: SHORING & RESHORING PLANS TO BE |
| | SUBMITTED AS A DEFERRED SUBMITTAL, TO BE REVIEWED BY |
| | THE ENGINEER OF RECORD, APPROVED BEFORE SUBMITTAL TO |
| | THE BUILDING DEPARTMENT. |
| | |
| | 5A-5E) BUILDING PROVISO: PRODUCT APPROVALS TO BE |
| | DEFERRED SUBMITTALS. |
| | |
| | 5B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 5C) DEFERRED. 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 5D) DEFERRED. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING . |
| | |
| | 5E) DEFERRED. FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED. IF SO |
| | RAS 117 CALCULATIONS ARE REQUIRED BY EITHER A FLORIDA |
| | ARCHITECT OR ENGINEER. |
| | 5F) COMPLIED. A/C STANDS. |
| | |
| | 6) BUILDING PROVISO/ DEFERRED SUBMITTAL: |
| | |
| | 6A) DEFERRED SUBMITTAL. NOTE THIS NOTE APPLIES TO |
| | FLOORS 2-4 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE |
| | SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| | OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) DEFERRED SUBMITTAL . THIS NOTE APPLIES TO WALLS AS |
| | WELL AS FLOORS!!! ON ALL FLOORS. WALL TYPES FOUND ON |
| | SHEET A8.01, THE WALL TYPES DO NOT PROVIDE THE REQUIRED |
| | STC RATING NOR TEST RESULTS IN ACCORDANCE WITH: FBC-B |
| | 2014 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND |
| | FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM |
| | EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 |
| | IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 90. |
| | |
| | 6C) DEFERRED SUBMITTAL. THIS IS A VERY RESTRICTIVE |
| | REQUIREMENT!!!!!! TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. INSULATING |
| | MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| | ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| | INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| | OF NOT MORE THAN 450. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 7) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & E5.01 |
| | CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5 |
| | AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR |
| | OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE |
| | WITH UL 325. IF THERE IS A POWER FAILURE OR A |
| | MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS |
| | HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 8) PROVISO: THE HEIGHT OF THE SLIDING GLASS DOOR SILL |
| | WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT |
| | APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 . |
| | |