Plan Review Notes
Plan Review Notes For Permit 16100611
Permit Number 16100611
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-15 15:24:471) SHT.A0.02 - THERE IS A CLOUDED NOTE THAT REFERS TO
 WOOD BLOCKING FOR FUTURE GRAB BARS IN FIRST FLOOR UNITS
 ONLY. REVISE NOTE TO INCLUDE ALL FLOORS PER THE FHA.
 2) SHEET A2.01 - REMOVE THE SHADING FROM THE FLOOR
 PLAN. THE CLEAR FLOOR SPACE AT THE PLUMBING FIXTURES IS
 DIFFICULT TO SEE. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. A2.02 - REMOVE THE SHADING FROM THE ROOF PLAN.
 THE ROOF DRAINS AND NOTES ARE EXTREMELY DIFFICULT TO
 SEE AND READ. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A8.03 - DETAIL #12 - COMBUSTIBLES ARE NOT
 PERMITTED IN THE A/C CLOSET SINCE IT IS A RETURN AIR
 PLENUM. MATERIALS WITHIN A PLENUM SHALL COMPLY WITH THE
 FLORIDA MECHANICAL CODE SEC.602.2.1. FLAME SPREAD INDEX
 NO MORE THAN 25 AND SMOKE -DEVELOPED INDEXOF NOT MORE
 THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL
 723. SUBMIT SPECIFICATIONS ON THE CPVC TO SHOW
 COMPLIANCE. SEE SHT.P6.01, GENERAL PLUMBING NOTES 11,
 13.
 5) SHT. P1.01 - THE HUB DRAIN AND FLOOR DRAIN IN THE
 TRASH ROOM AND IN THE DOMESTIC PUMP ROOM SHALL BE
 EQUIPPED WITH TRAP PRIMERS. 2014 FPC SEC.1002.4.
 6) SHT. P5.01 - THE WATER FOR THE JANITOR SINKS ON THE
 SECOND AND THIRD FLOORS HAS BEEN DELETED FROM THE RISER
 BUT THE SANITARY RISER STILL SHOWS THE DRAINS. CLARIFY.
 7) SHT. A2.01 - UNITSA.1 & A.1R - THE DOOR IN THE
 MASTER BATH SWINGS INTO THE REQUIRED CLEAR FLOOR SPACE
 FOR THE FIXTURES PER THE FHA GUIDELINES.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW