| 2016-11-15 15:24:47 | 1) SHT.A0.02 - THERE IS A CLOUDED NOTE THAT REFERS TO |
| | WOOD BLOCKING FOR FUTURE GRAB BARS IN FIRST FLOOR UNITS |
| | ONLY. REVISE NOTE TO INCLUDE ALL FLOORS PER THE FHA. |
| | 2) SHEET A2.01 - REMOVE THE SHADING FROM THE FLOOR |
| | PLAN. THE CLEAR FLOOR SPACE AT THE PLUMBING FIXTURES IS |
| | DIFFICULT TO SEE. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHT. A2.02 - REMOVE THE SHADING FROM THE ROOF PLAN. |
| | THE ROOF DRAINS AND NOTES ARE EXTREMELY DIFFICULT TO |
| | SEE AND READ. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. A8.03 - DETAIL #12 - COMBUSTIBLES ARE NOT |
| | PERMITTED IN THE A/C CLOSET SINCE IT IS A RETURN AIR |
| | PLENUM. MATERIALS WITHIN A PLENUM SHALL COMPLY WITH THE |
| | FLORIDA MECHANICAL CODE SEC.602.2.1. FLAME SPREAD INDEX |
| | NO MORE THAN 25 AND SMOKE -DEVELOPED INDEXOF NOT MORE |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723. SUBMIT SPECIFICATIONS ON THE CPVC TO SHOW |
| | COMPLIANCE. SEE SHT.P6.01, GENERAL PLUMBING NOTES 11, |
| | 13. |
| | 5) SHT. P1.01 - THE HUB DRAIN AND FLOOR DRAIN IN THE |
| | TRASH ROOM AND IN THE DOMESTIC PUMP ROOM SHALL BE |
| | EQUIPPED WITH TRAP PRIMERS. 2014 FPC SEC.1002.4. |
| | 6) SHT. P5.01 - THE WATER FOR THE JANITOR SINKS ON THE |
| | SECOND AND THIRD FLOORS HAS BEEN DELETED FROM THE RISER |
| | BUT THE SANITARY RISER STILL SHOWS THE DRAINS. CLARIFY. |
| | 7) SHT. A2.01 - UNITSA.1 & A.1R - THE DOOR IN THE |
| | MASTER BATH SWINGS INTO THE REQUIRED CLEAR FLOOR SPACE |
| | FOR THE FIXTURES PER THE FHA GUIDELINES. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |