| Notes |
| Date |
Text |
| 2016-11-02 10:21:03 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100611 | | | 11/2/16 | | | | | | 1) SUBMIT ENERGY CALCULATIONS AND AC COOLING AND | | | HEATING CALCULATIONS. | | | | | | 2) SHEET M501: MECHANICAL VENTILATION RATES CANNOT BE | | | USED TO VERIFY COMPLIANCE WITH THE NATURAL VENTILATION | | | REQUIREMENT FOR THE GARAGES. PLEASE REVIEW SECTIONS | | | 401.2 AND 402.2 AND PROVIDE THE CORRECT CALCULATIONS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|