2016-12-29 15:29:26BUILDING PLAN REVIEW
 W. P. B. REVISION: 16100600
 W. P. B. PERMIT: 15060551 M1-M4 SLUDGE PUMPING &
 BOILER/ GAS HANDILING BUILDING
 ADD: 4395 EASLEY ST.
 CONT: POOLE & KENT
 CONTACT: KURT PFEFFER, P. E.
 TEL:
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. DEC. 29/ 2016
 ACTION: DENIED
  
 1) THE SHEET 0385-A-ADF-07 IS NOT A SUBMITTAL BUT A
 REVISION. IN THE ORIGINAL PERMIT DOCUMENT SET OF PLANS
 V2 SHOWED A REVISION NUMBER (3) DATED 10/15. IN THE
 LATEST SET OF PLANS SUBMITTED, THERE IS A REVISION # 4.
 THE NEW VERSION # 2 DOES NOT AND ORIGINAL ARE
 IDENTICAL. IN BOTH CASES REVISION # 4 SHOWS AS EXISTING
 REVISION. THE FOR REFERENCE ONLY IS WHEN THERE ARE
 PLANS ALREADY ON FILE AND NO CHANGES HAVE BEEN MADE.
 THESE PLANS ARE A REVISION REQUIRING FEES AND THEY WILL
 ALSO NEED THE ENGINEER OF RECORD TO ELECTRONICALLY SIGN
 AND SEAL PLANS. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) THE SHEET BOILER-GAS HANDLING BUILDING, ROOF PLAN
 HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0386-A-ADF-08 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 3) THE SUBMITTED SHEET M1-M4 SLUDGE PUMPING BUILDING
 ROOF PLAN HAS BEEN RENAMED, PLEASE KEEP THE SAME NAMING
 NOMENCLATURE, THIS SHEET IS: 0387-A-ADF-09 THIS SHEET
 DOES NOT SHOW ANY REVISIONS OTHER THAN THE NEW NAMING
 CONVENTION. THE REVISION IS BEING THE SHEET RENAMED,
 STAFF TIME IN RESEARCHING HAS TO BE PAID. SINCE THIS IS
 CONSIDERED A REVISION THE SHEET WILL ALSO NEED TO
 COMPLY WITH 61G15-23.005.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  