2016-10-26 08:57:39BUILDING PLAN REVIEW
 W. P. B. REVISION: 16100599
 W. P. B. PERMIT: 15060558
 ADD: 4395 EASLEY DR. FERRIC CHLORIDE FACILITY/
 PRE-ENGINEERED METAL BUILDING SHOP DRAWINGS
 CONT: POOLE & KENT
 TEL: WILLIAM VENEGAS
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: WED. OCT. 26/ 2016
  
 ACTION: BUILDING PROVISO
  
 BUILDING PROVISO: FRAME WORK ONLY APPROVED. IN THIS
 SUBMITTAL THERE WAS NO ROOFING OR WALL PRODUCT
 APPROVALS SUBMITTED TO VERIFY SPANS OR GAUGE THICKNESS
 FOR THESE MATERIALS. IF THE ROOFING OR WALL SYSTEM
 REQUIRE CLOSER GIRTS AND PURLINS A REVISION WILL BE
 REQUIRED FOR THE FRAMING SYSTEM OF THE BUILDING.
  
 2014 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  