| Date |
Text |
| 2016-10-26 17:17:32 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| | |
| | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES |
| | |
| | (1) PROVIDE MECHANICAL PLANS AS PER 107.2.1.4. (SEE |
| | ABOVE). |
| | (2) DESIGNATE EXISTING AND NEW DUCTWORK, IF APPLICABLE. |
| | (3) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1 |
| | (4) SHOW LOCATION OF CONDENSERS. |
| | (5) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014 |
| | (6) PROVIDE EXHAUST IN ALL BATHROOMS. |
| | (7) PROVIDE RETURN FROM ALL BEDROOMS. |
| | |
| | FLORIDA ENERGY CODE FBC 2014 |
| | |
| | R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| | IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| | DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| | MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| | UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| | THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| | CONDITIONS DESCRIBED IN |
| | SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER |
| | SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR |
| | OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM |
| | SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY |
| | LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS |
| | STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. |
| | |
| | (8) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE |
| | ABOVE). SUMMARIES ARE NOT ACCEPTABLE. |
| | |
| | JORGE VALIDO |
| | WPB MECHANICAL INSPECTOR/PLANS EXAMINER |
| | [email protected] |
| | 561-805-6716 |
| | |
| | |