| Plan Review Notes For Permit 16100579 |
| Permit Number |
16100579 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-26 16:22:20 | 1ST REVISION 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] CLEARLY DEFINE THE SCOPE OF WORK TO A ALTERATION | | | LEVEL 2 PER THE EXISTING FBC 2014 SECTION 504. | | | | | | 2] PROVIDE THE EXISTING ELECTRIC SERVICE RISER WITH | | | WIRE AND CONDUIT SIZES, AND GROUNDING DETAIL. SHOW | | | COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES WITH | | | MATCHING CIRCUITS ON FLOOR PLAN. FBC- 107.3.5.3 | | | | | | 3] MISSING A RECEPTACLE OUTLET PER SPACING REQUIREMENTS | | | IN THE MASTER BATH WALL FACING THE MASTER SUITE. FBC-R | | | SECTION E3901.1.2.1 | | | | | | 4] ADD A GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT | | | RECEPTACLES ACCORDING WITH FBC-R SECTION E4002.14 |
|