| Permit Number |
16100550 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-03-09 14:19:57 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS ON THE POOL | | | HEATERS. WPB AMEND. TO FBC SEC.107.2.1. | | | 2) GAS FIRED POOL HEATERS SHALL HAVE A MINIMUM THERMAL | | | EFFICIENCY OF 82 PERCENT PER 2014 FBC-ENERGY, TABLE | | | C404.2, SEC.C404.7.1. | | | 3) ALL POOL HEATERS SHALL BE EQUIPPED WITH A READILY | | | ACCESSIBLE ON-OFF SWITCH THAT IS MOUNTED OUTSIDE OF THE | | | HEATER TO ALLOW SHUTTING OFF THE HEATER WITHOUT | | | ADJUSTING THE THE THERMOSTAT SETTING.GAS - FIRED | | | HEATERS SHALL NOT BE EQUIPPED WITH CONSTANT BURNING | | | PILOT LIGHTS.2014 FBVC- ENERGY SEC.C404.7.1. | | | 4) THE GAS POOL HEATERS SHALL BE LISTED AND LABELED PER | | | THE 2014 FBC-FUEL GAS SEC. 301.3. | | | 5) THE MANUFACTURER'S INSTALLATION MANUAL FOR THE POOL | | | HEATERS SHALL BE ON THE JOBSITE FOR INSPECTION. 2014 | | | FBC - FUEL GAS SEC.305.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|