| 2016-10-26 14:32:23 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] ACCORDING TO YOUR LOAD CALCULATION AND RISER DIAGRAM | | | THE INTERIOR 100 AMP PANEL WILL HANDLE THE ENTIRE 119 | | | AMP LOAD OF THE HOUSE THEREFORE UNDERSIZED PER NEC | | | 215.2 MINIMUM RATING & SIZE OF FEEDERS. PLEASE UPGRADE | | | INTERIOR PANEL OR PROVIDE A CALCULATION BREAKDOWN WITH | | | PANEL SCHEDULES IDENTIFYING EACH LOAD. FBC-107 | | | | | | 2] NEC 250.94 BONDING FOR OTHER SYSTEMS. THE | | | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE | | | INSTALLED. |
|