2016-10-24 15:18:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET 6 OF 7 SHOWS S(SMOKE) N1L1S59; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT AS ! (HEAT).
  
  
 2) SHEET 5 OF 7 SHOWS S, N1L1S43; HOEVER, ON SHEET 6 OF
 7 IT COULD NOT BE LOCATED.
  
  
 3) SHEET 6 OF 7 SHOWS SCF 3-4, N1L1S70; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S69.
  
  
 4) SHEET 6 OF 7 SHOWS FCU 2-1, N1L1S43; HOWEVER, ON
 SHEET 4 OF 7 ITS SHOWS IT AS N1L1S39.
  
  
 5) SHEET 6 OF 7 SHOWS FCU 3-2, N1L1S66; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S68.
  
  
 6) SHEET 6 OF 7 SHOWS SCF 3-1, N1L1S72; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S71.
  
  
 7) SHEET 6 OF 7 SHOWS FCU 3-7, N1L1S73; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S72.
  
  
 8) SHEET 6 OF 7 SHOWS FCU 3-6, N1L1S77; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S73.
  
  
 9) SHEET 6 OF 7 SHOWS FCU 3-5, N1L1S75; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S74.
  
  
 10) SHEET 6 OF 7 SHOWS SCF 3-3, N1L1S77; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S75.
  
  
 11) SHEET 6 OF 7 SHOWS SCF 3-2, N1L1S79; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S77.
  
  
 12) SHEET 6 OF 7 SHOWS SCF 3-5, N1L1S76; HOWEVER, ON
 SHEET 5 OF 7 IT COULD NOT BE LOCATED.
  
  
 13) SHEET 6 OF 7 SHOWS AHU 3-1, N1L1S78; HOWEVER, ON
 SHEET 5 OF 7 IT SHOWS IT A N1L1S76.
  
  
 14) SHEET 6 OF 7 SHOWS S , N1L1S68; HOWEVER, ON SHEET 5
 OF 7 IT COULD NOT BE LOCATED.
  
  
 15) SHEET 6 OF 7 A "C" INSIDE A SQUARE BOX IS
 INDICATED; HOWEVER, ON SHEET 7 OF 7 IT IS NOT
 IDENTIFIED IN THE LEGEND.
  
  
 16) SHEET 7 OF 7 A "T" INSIDE A SQUARE BOX IS
 INDICATED; HOWEVER, ON SHEET 7 OF 7 IT IS NOT
 IDENTIFIED IN THE LEGEND.
  
  
 18) SHEET 7 OF 7, THE ABOVE DEVICES, COUNTS AND
 VOLTAGES MAY NEED TO BE UPDATED IN EACH OF THE
 APPLICABLE CALCULATION TABLES.
  
  
 19) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR
 NUMBERED NARRATIVE RESPONSES TO THE ABOVE ON
 RESUBMITTAL.
  
  
 20) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  