| Plan Review Notes For Permit 16100404 |
| Permit Number |
16100404 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-20 15:21:11 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] CLARIFY IF EACH METER ENCLOSURE HAS A MAIN | | | DISCONNECT ? ALL MAINS MUST BE GROUPED AT THE SERVICE | | | PER NEC 230.72 | | | | | | 2] SHOW EXISTING SERVICE WIRE AND CONDUIT SIZES ON THE | | | RISER, IDENTIFY AMPERE RATING OF EXISTING EQUIPMENT AND | | | LABEL EACH DISCONNECT, PROVIDE A SITE SPECIFIC FLOOR | | | PLAN INDICATING THE LOACTION OF EACH PANEL. | | | FBC-107.3.5.3 | | | | | | 3] MISSING 2 SMALL APPLIANCE VA LOADS ON THE | | | CALCULATION, ASWELL AS THE WASHER CIRCUIT. IF THE | | | BUILDING HAS A COMMON LAUNDRY PLEASE SPECIFY ON THE | | | CALCS. NEC 220.52(A)&(B) | | | | | | 4] ACCORDING TO NEC 220.82 OPTIONAL FEEDER AND SERVICE | | | LOAD CALCULATIONS ONLY APPLY TO 120-240 VOLTS 3 WIRE | | | CONDUCTORS WITH AN AMPACITY OF 100 AMP OR GREATER. | | | ( YOUR LOAD SIZE IS 70 AMPS THEREFORE YOU MUST USE THE | | | STANDARD METHOD IN ACCORDANCE WITH NEC 220 PART 3 ) | | | | | | |
|