| Plan Review Notes For Permit 16100393 |
| Permit Number |
16100393 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-01 17:52:37 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SPECIFY WHICH TYPE OF ROOF WILL BE ROOFED OVER AND | | | WHICH WILL BE REMOVED TO THE ROOF DECK. FBC 107.2.1 THE | | | DESCRIPTION OF WORK ON THE PERMIT APPLICATION STATES | | | THAT THE SHINGLES WILL BE A RECOVER (ROOF OVER). THIS | | | NEEDS TO BE CROSSED OUT, BY THE APPLICANT, AND CHANGED | | | TO "REROOF" ON THE APPLICATION. FBC 107.2.1 | | | | | | 2) THE SIGNED AND SEALED RAS 117 CALCULATIONS THAT WERE | | | SUBMITTED FOR THE FLAT ROOF CONTAINS SEVERAL ERRORS. | | | THE FASTENER SPACING OF THE TWO ROWS IN THE FIELD IS 9" | | | O.C. FOR THE E(2) SYSTEM WITH THE MAXIMUM DESIGN | | | PRESSURE OF -60 PSF ON PAGE 28 OF NOA NO. 14-1030.02. | | | THIS ERROR CAUSES ALL OF YOUR NAILING REQUIREMENTS TO | | | ALSO BE IN ERROR. PLEASE CORRECT. FBC 107.2.1.3 | | | | | | 3) THE VALUATION FOR THE WORK HAS BEEN INCREASED FROM | | | $8,250.00 TO $11,860 BASED ON THE LATEST MARSHALL | | | VALUATION DATA. FBC 109.3 | | | | | | | | | | | | |
|