| 2016-12-08 16:16:56 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | PLEASE SEE 1ST REVIEW COMMENTS BELOW WHICH ARE STILL |
| | APPLICABLE BASED ON THE RESUBMITTAL. NOTE THE |
| | RE-SUBMITTAL CONTAINS NOTES, MODIFICATIONS, AND |
| | DRAWINGS PLACED ON THE PLAN BY SOMEONE OTHER THAN THE |
| | RESPONSIBLE DESIGN PROFESSIONAL. THE PLAN CONTAINS |
| | MECHANICAL INDICATIONS THAT AN EXISTING GARAGE HAS AN |
| | EXISTING SYSTEM WHICH DOES NOT NEED TO BE MODIFIED. |
| | THEIS IS INCONSISTENT WITH THE PREVIOUS PLAN BY A |
| | DESIGNER AND CITY PERMIT RECORDS. AS ORIGINALLY |
| | INDICATED BELOW, AN ENERGY SUBMITTAL AND A MECHANICAL |
| | PLAN IS REQUIRED. |
| | |
| | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | |
| | A MECHANICAL DESIGN IS REQUIRED. THE PLAN NOTES |
| | INDICATE HVAC BY OTHERS. PLEASE COORDINATE THE DESIGN |
| | WITH THE RE-SUBMITTAL FOR THIS PROJECT. IT MUST INCLUDE |
| | AN ENERGY SUBMITTAL. |
| | |
| | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| | |
| | ALTERNATIVELY |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | |
| | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW |
| | SUPPLY DUCTS PER FBC-R M16 |
| | |
| | |