| Plan Review Notes For Permit 16100392 |
| Permit Number |
16100392 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-26 09:12:19 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] CLARIFY IF PROPOSED "NEW GAME ROOM" WILL BE A | | | SLEEPING AREA. THEREFORE IF DEFINED AS A SLEEPING ROOM | | | PROVISIONS FOR SMOKE ALARMS IN ACCORDANCE WITH FBC-R | | | SECTIONS 314 & 315 WILL APPLY. | | | | | | 2] ADD A GENERAL ELECTRICAL NOTES FOR TAMPER-RESISTANT | | | AND AFCI PROTECTION PER FBC-R SECTIONS E4002.14 & | | | E3902.13 |
|