2016-10-20 09:14:35PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS FOR THE 2ED FLOOR
 ADDITION
 PER SECTION 403.2.1 FLORIDA ENERGY CODE 2014
 2) PROVIDE EQUIPMENT SCHEDULE ON PLANS FOR
 AIR CONDITIONING EQUIPMENT. PER SECTION 107 FBC 2014
 3) PROVIDE DUCT SIZE ON THE PLAN.
 PER SECTION 107 FBC 2014
 4) THERE WAS NO AIR CONDITIONING PLAN SUBMITTED FOR THE
 2ED FLOOR
  
 PLAN REVIEW BY HAROLD MOSER