2016-11-29 18:01:162ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16100301
 11/29/16
  
 1) COMMENTS FORM THE 1ST REVIEW STILL EXIST. NO
 MECHANICAL PLANS HAVE BEEN SUBMITTED. SEE 1ST REVIEW
 COMMENTS PRINTED BELOW.
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100301
 10/19/16
  
 1) PROVIDE A DUCT LAYOUT PLAN FOR THE RELOCATED AIR
 HANDLER- SHOW TYPES AND SIZES OF SUPPLY AND RETURN
 DUCTS AND POINTS OF CONNECTIONS TO EXISTING DUCTWORK.
 INDICATE LOCATIONS OF FIRE OR FIRE/SMOKE DAMPERS AND
 PROVIDE INSTALLATION DETAILS.
  
 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE RELOCATED AIR
 HANDLER- MAKE AND MODEL, COOLING AND HEATING CAPACITY.
  
 3) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION AND INDICATE THE TYPE OF DOOR TO BE
 INSTALLED AT THE AC CLOSET. PLEASE NOTE IF THE DOOR IS
 LOUVERED FOR RETURN AIR IT MUST BE MADE OF
 NON-COMBUSTIBLE MATERIAL.
  
 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  