| Plan Review Notes For Permit 16100301 |
| Permit Number |
16100301 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-11-29 18:01:16 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100301 | | | 11/29/16 | | | | | | 1) COMMENTS FORM THE 1ST REVIEW STILL EXIST. NO | | | MECHANICAL PLANS HAVE BEEN SUBMITTED. SEE 1ST REVIEW | | | COMMENTS PRINTED BELOW. | | | | | | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100301 | | | 10/19/16 | | | | | | 1) PROVIDE A DUCT LAYOUT PLAN FOR THE RELOCATED AIR | | | HANDLER- SHOW TYPES AND SIZES OF SUPPLY AND RETURN | | | DUCTS AND POINTS OF CONNECTIONS TO EXISTING DUCTWORK. | | | INDICATE LOCATIONS OF FIRE OR FIRE/SMOKE DAMPERS AND | | | PROVIDE INSTALLATION DETAILS. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE RELOCATED AIR | | | HANDLER- MAKE AND MODEL, COOLING AND HEATING CAPACITY. | | | | | | 3) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY | | | CONSERVATION AND INDICATE THE TYPE OF DOOR TO BE | | | INSTALLED AT THE AC CLOSET. PLEASE NOTE IF THE DOOR IS | | | LOUVERED FOR RETURN AIR IT MUST BE MADE OF | | | NON-COMBUSTIBLE MATERIAL. | | | | | | 4) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | | | | |
|