| 2016-10-26 11:25:25 | JOB PERMIT NUMBER: 16100301 | | | JOB ADDRESS: 603 VILLAGE BLVD SUITE #208 | | | WEST PALM BEACH FLORIDA | | | DATE: OCTOBER 26, 2016 | | | ELECTRICAL PLAN REVIEW COMMENTS | | | | | | - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC | | | 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA | | | BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH | | | AMENDMENTS. BELOW IS A LIST OF THE ITEMS NOTED. | | | | | | 1] PROVIDE EMERGENCY LIGHTING IN THE FLOOR SPACE AREA | | | WHERE THE NEW A/C CLOSET IS LOCATED. FBC-1006.1 | | | ILLUMINATION REQUIRED. | | | | | | 2] EXITS & EMERGENCY LIGHTS SHALL BE FED BY THE LOCAL | | | LIGHTING CIRCUIT IN THAT AREA. NEC 700.12(F)(4) SHOW | | | COMPLIANCE. | | | | | | 3] CLARIFY IF RECEPTACLE OUTLETS BY THE BREAKROOM SINK | | | HAVE GFCI PROTECTION PER NEC 210.8(B)(5) | | | | | | 4] ADD A NOTE FOR QUICK-BREAK DISCONNECTS IN | | | FLUORESCENT FIXTURES IN ACCORDANCE WITH NEC 410.130(G) | | | | | | - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE | | | MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER | | | RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES | | | WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER | | | QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME | | | DIRECTLY. | | | | | | 1ST REVIEW, FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | |
|