| Plan Review Notes For Permit 16100277 |
| Permit Number |
16100277 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-11-09 07:30:22 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | ****ISSUED AT CONTRACTOR'S RISK*** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE SOUTH EXTERIOR ENTRY DOOR ON THE FLOOR PLAN (PERMIT | | | 16100277) AND THE NORTH INTERIOR SECURITY VESTIBULE | | | DOORS SHOWN ON THE FLOOR PLAN AS "EXISTING" HAVE DOOR | | | SWING CONFIGURATION WHICH ARE NOT CONSISTENT WITH THE | | | PERMIT ISSUED FOR THIS SCOPE OF WORK, EXPIRED ENTRY | | | SECURITY VESTIBULE PERMIT 14020726, NEW "FINAL | | | INSPECTION ONLY" PERMIT 16110426. | | | | | | PRIOR TO FINAL INSPECTION, THE TWO PLANS SHOULD | | | CORRELATE AND SHOULD MATCH THE EXISTING CONDITIONS. A | | | REVISION IS REQUIRED. | | | | | | THIS PERMIT IS ISSUED AT CONTRACTOR'S RISK. THE NEW | | | PROPOSED (NOT YET SUBMITTED FOR PLAN REVIEW) | | | CONFIGURATION IS TO BE SUBMITTED AND APPROVED AS A | | | REVISION (TO 16110426) PRIOR TO FINAL INSPECTION. OR, | | | THE INSTALLATION CAN BE MODIFIED TO BE CONSISTENT WITH | | | THE ISSUED PERMIT. IN THAT CASE, THE "FINAL INSPECTION | | | ONLY" PERMIT 16110426 SHOULD BE MODIFIED TO A "REISSUE" | | | PERMIT AND THE FLOOR PLAN FOR RENOVATION PERMIT | | | 16100277 REVISED TO BE CONSISTENT. | | | | | | | | | | | | |
|