| 2016-11-04 10:32:11 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100277 | | | 11/4/16 | | | | | | 1) SUBMIT AHRI CERTIFICATES FOR THE AC SYSTEMS TO | | | VERIFY THAT THE REPLACED AIR HANDLERS MATCH THE | | | EXISTING CONDENSERS | | | | | | 2) THE 18X10 AND 12" TRANSFER DUCTS AT THE BREAKROOM | | | AND BOLD SPACE ARE UNDERSIZED PER SECTION 601.5 | | | EXCEPTION 1. PLEASE PROVIDE THE TRANSFER AND RETURN | | | GRILL SIZES ON THE PLANS. | | | | | | 3) INDICATE THE TYPE OF LOUVERED DOORS THAT ARE | | | ENCLOSING THE MECHANICAL CLOSET AND CONVEYING RETURN | | | AIR. PLEASE NOTE THAT THE DOORS MUST BE NON-COMBUSTIBLE | | | PER SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|