Plan Review Notes
Plan Review Notes For Permit 16100277
Permit Number 16100277
Review Stop B
Sequence Number 2
Notes
Date Text
2016-11-03 16:37:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. THE SECURITY VESTIBULE PERMIT IS EXPIRED. THE PLAN
 SHOWS THIS AS EXISTING, BUT IT IS EXISTING (FOR
 BUILDING CODE PURPOSES) ONLY IF IT WAS LEGALLY
 PERMITTED, CONSTRUCTED AS PERMITTED, AND FINALED. THE
 PLAN SHOWS THAT THE CONSTRUCTION IS NOT CONSISTENT WITH
 THE ISSUED PERMIT, DOES NOT APPEAR TO COMPLY WITH
 ACCESSIBILITY MANEUVERING CLEARANCE REQUIREMENT ON THE
 PULL SIDE, AND NO BUILDING INSPECTIONS WERE SCHEDULED
 (ONLY FIRE INSPECTIONS).
  
 EITHER APPLY FOR A SEPARATE PERMIT FOR THE VESTIBULE
 WORK, OR INCORPORATE THAT WORK INTO THIS PERMIT. SEE
 EXPIRED PERMIT 14020726. YOU MAY OBTAIN A COPY OF THE
 PLAN FOR THAT PERMIT BY SUBMITTING A REQUEST TO
 [email protected].
  
 2ND REVIEW, THE EXPIRED PERMIT HAS NOT BEEN ADDRESSED.
 THE WORK INSTALLED IS NOT CONSISTENT WITH THE ISSUED
 PERMIT. C M FREEMAN IS TO SUBMIT APPLICATION FOR A
 PERMIT FOR THAT WORK. PLEASE ADVISE WHEN THIS HAS BEEN
 DONE AND THE BUILDING REVIEW WILL BE PASSED (PENDING
 ITEM 3).
  
 2. OK
  
 3. SHEET A4.1 REFERS TO FBC 2007 IN MORE THAN ONE
 LOCATION, REVISE.
  
 THIS HAS BEEN REVISED TO FBC 2012, ALSO REFERS TO FBC
 ADA 2012, THE CODE IN EFFECT IS FBC 5TH EDITION OR FBC
 2014.
  
 THIS MAY BE A PROVISO ITEM UPON REQUEST.
  
 4, 5, 6. OK
  
  