Plan Review Notes
Plan Review Notes For Permit 16100277
Permit Number 16100277
Review Stop P
Sequence Number 1
Notes
Date Text
2016-10-21 10:28:351ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE GRAB BARS SHALL BE MEASURED FROM THE TOP OF THE
 GRIPPING SURFACE TO FINISH FLOOR AND BE MIN 33" MAX
 36". PER FBC ACC 609.4
  
 2. TH TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 3. LAVATORY'S SHALL BE SUPPLIED WITH TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. SHT. P-1.1 THE FLOOR PLAN DID NOT COPY WELL IT IS
 VERY LIGHT AND SOME OF THE WALLS AND FIXTURES CAN NOT
 BE SEEN PLEASE PROVIDE A DARKER COPY. PER WPB AMEND TO
 FBC 107.2.1.4
  
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1