| 2016-10-21 10:28:35 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE GRAB BARS SHALL BE MEASURED FROM THE TOP OF THE |
| | GRIPPING SURFACE TO FINISH FLOOR AND BE MIN 33" MAX |
| | 36". PER FBC ACC 609.4 |
| | |
| | 2. TH TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| | 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| | INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| | SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| | NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| | NOT ALLOW CONTINUOUS PAPER FLOW. |
| | |
| | 3. LAVATORY'S SHALL BE SUPPLIED WITH TEMPERED WATER. |
| | PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | |
| | 4. SHT. P-1.1 THE FLOOR PLAN DID NOT COPY WELL IT IS |
| | VERY LIGHT AND SOME OF THE WALLS AND FIXTURES CAN NOT |
| | BE SEEN PLEASE PROVIDE A DARKER COPY. PER WPB AMEND TO |
| | FBC 107.2.1.4 |
| | |
| | 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1 |