| Plan Review Notes For Permit 16100277 |
| Permit Number |
16100277 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-19 15:52:29 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16100277 | | | 10/19/16 | | | | | | 1) CLARIFY HOW THE O/A MOTORIZED DAMPER FOR AHU-1 & | | | AHU-2 WILL FUNCTION INDIVDUALLY FOR EACH SYSTEM. | | | | | | 2) LEVEL-2 ALTERATIONS SHALL BE IN COMPLIANCE WITH THE | | | CURRENT CODES IN EFFECT- SEE SECTION 801.3 FBC-14 | | | EXISTING BUILDING CODE. PROVIDE DUCT SMOKE DETECTORS IN | | | THE RETURN AIR SYSTEMS OF THE REPLACED AIR HANDLERS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|