2016-10-19 09:51:10INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS,ETC. A NOTE WILL SUFFICE.
 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS; SEE VERBIAGE IN CODE.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16- ARC FLASH WARNING; SEE VERBIAGE IN
 CODE.
 4. PERE NEC 110.15- PROVIDE NOTE FOR HIGH LEG MARKINGS
 REQUIREMENTS AT THE SERVICE AND PANELBOARDS. SEE NEC
 408.2F1
 5. PER FBC-EC 405.7- A MINIMUM OF 50% OF ALL
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED FOR
 OFFICE AREAS. SHOW COMPLIANCE
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  