| Plan Review Notes For Permit 16100277 |
| Permit Number |
16100277 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-10-19 09:51:10 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW | | | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE | | | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS | | | SYSTEMS,ETC. A NOTE WILL SUFFICE. | | | 2. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD | | | MARKINGS; SEE VERBIAGE IN CODE. | | | 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO | | | INDICATE NEC 110.16- ARC FLASH WARNING; SEE VERBIAGE IN | | | CODE. | | | 4. PERE NEC 110.15- PROVIDE NOTE FOR HIGH LEG MARKINGS | | | REQUIREMENTS AT THE SERVICE AND PANELBOARDS. SEE NEC | | | 408.2F1 | | | 5. PER FBC-EC 405.7- A MINIMUM OF 50% OF ALL | | | RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED FOR | | | OFFICE AREAS. SHOW COMPLIANCE | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|